Page 15 of European Technical Approval ETA-11/0390, issued on 27.08.2012
English translation prepared by CSTB
 
 
 
 
 
 
of  the European
Technical Approval
 
ETA - 11/0390
Injection System Hilti HIT-CT 1 for rebar connection
 
Figure 10:
 
General design rules of construction for bonded-in rebars
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
1)
 
If the clear distance between lapped bars exceeds 4d
s
, then the lap length shall be increased by the difference
between the clear bar distance and 4d
s.
 
 
 
The following applies to Figure 10:
 
v
or.
0
are in accordance with section 4.3.2 of the approval
 
The provision of sufficient transverse reinforcement according to section 4.3.2.6 of this approval  
must be verified.
 
c
concrete cover of bonded-in bar
c
1
 
concrete cover at end-face of bonded-in bar
min c
minimum concrete cover acc. Annex 8 of this approval
d
s
 
diameter of bonded-in bar
0
 
lap length
v
 
effective embedment depth
d
0
 
nominal drill bit diameter, see Table 7 to Table 9
 
 
 
 
 
 
Annex 5
 
General design rules of construction
spacing and edge distance  
for bonded-in rebars
 
member edge
bonded-in bars
c
    
 
min c
 
 
5 d
s
 
d
0
 
 
 
8mm    
 
 
d
s
 
 
 
25mm
50mm
 
0
 
c
1
 
 
v
 
4 d
s
 
1)